What to do about that pesky R-22 chiller: Part I - HPAC Magazine (2024)

While there have not been any widespread shortages of R-22 to date, the price has certainly been reflective of a reduced supply. With a complete ban on new R-22 (either imported or manufactured) beginning January 2020, the supply will continue to reduce. That likely means continued increases in price.

So, what are the options for those R-22 chillers still in use? Certainly, replacing an older R-22 chiller with a new, more efficient chiller is always desirable but it is not always practical in a budgetary sense.

Let’s review the procedure for undertaking a refrigerant conversion for R-22 chillers starting with the refrigerant selection. Part II in HPAC December 2018 will address the conversion procedure.

CHOOSING THE R-22 REPLACEMENT

Table 1 Chemical composition of R-22 replacements

Table 1 is a list of the available R-22 replacements. There are essentially four main building blocks for all of these refrigerants; R-32, R-125, R-134A and R-143A.

There are many R-22 replacement choices available and each has its plusses and minuses. Just as there were no perfect replacements for R-12 or R-502, there is no perfect replacement for R-22. And while the term drop-in seems to be freely used in reference to R-22 replacements, there are no replacements that you can simply drop-in in place of R-22 and walk away without any further concern.

The fact is there is no single R-22 replacement that has properties identical to R-22. Since each refrigerant has its own particular set of thermodynamic properties, it stands to reason that each refrigerant will have its own specific capacity compared to R-22, mass flow rate compared to R-22 and efficiency compared to R-22.

The following are three of the crucial pieces of information in determining the best choice as a replacement for R-22.

1. System capacity with new refrigerant (compared to R-22): This is pretty self-explanatory. If you have a 75-ton chiller and the particular application requires all of that 75 tons to maintain the design temperature, then a reduction in capacity would not be acceptable. Typically, the capacity for the R-22 replacement should have a capacity that is fairly close to the original system capacity with R-22.

2. Refrigerant mass flow rate with new refrigerant (compared to R-22): This might not be quite so self-explanatory, but still important in terms of complexity and expense of the conversion. The thermodynamic properties will determine what the refrigerant mass flow rate will be in a given application. TEV capacity is based on physical dimensions of the valve pin and port, system conditions and thermodynamic properties of the refrigerant.

If the mass flow requirement of the replacement refrigerant is significantly greater than the mass flow requirement for R-22, than the existing R-22 TEV would have insufficient capacity for the replacement refrigerant.

Table 2 TEV capacity with R-22 replacements

Table 2 shows a Thermostatic Expansion Valve (TEV) selection for a 10-ton AC application with R-22. An OVE-10 was selected, and it is operating at 99 per cent of its rated capacity at the design condition.
The table shows eight R-22 replacements, and how the R-22 TEV selection fares with each of the new refrigerant possibilities.

With R-407A and R-407C having similar mass flow rates to R-22, the original R-22 TEV selection is very suitable for application with both refrigerants. The others on the chart do not fare so well. Each has a greater mass flow requirement than R-22, resulting in the original R-22 TEV being undersized for each. The most notable capacity deficiency is with R-434A. In addition, the manufacturer of R-434A states that their refrigerant requires a TEV element that is compatible with R-502 (R-404A).

Certainly, there is no problem using any of these refrigerants as a replacement for R-22. But the TEV replacement adds cost and complexity to the conversion.A note regarding chillers with electronic expansion valves (EEVs): while there is no compatibility issue regarding the use of the R-22 EEV with any of these R-22 replacements, it is important to investigate whether the EEV controller was programmed with the ability to operate with the refrigerant you’re planning on using. This might be the determining factor in which refrigerant is chosen. Worst case scenario is that the controller was only programmed to be used with R-22. This would then require replacing or upgrading the controller, or forgoing the conversion.

3. System efficiency with the new refrigerant (compared to R-22): This is often overlooked. However, a refrigerant that has a reduced efficiency compared to R-22 will result in increased electrical consumption. This should also be a consideration, as operating expenses accrue every month.

In addition to the factors listed above, the following might be secondary factors, which would be considered:

  • Pressure-Temperature relationship of the conversion refrigerant
  • Has compressor manufacturer evaluated compressor performance and wear with conversion refrigerant?
  • Oil requirements of the conversion refrigerant
  • Environmental concerns (GWP of the conversion refrigerant)
  • Price and availability of the conversion refrigerant

Table 3 shows the more common R-22 replacements, showing capacity relative to R-22, mass flow relative to R22, and efficiency relative to R-22 when applied in a comfort cooling application.

Looking over this list of replacements, with the parameters listed, it becomes easier to make an educated choice. For example:

  • R-404A shows to have good capacity compared to R-22. However, with a 42 per cent greater mass flow requirement, a TEV replacement will be required. In addition, it has a nine per cent reduction in efficiency.
  • R-417A shows to have a good mass flow requirement compared to R-22, meaning that a TEV replacement will not be required. But a 14 per cent capacity loss would likely not be the best choice.
  • R-407C show a slight increase in capacity compared to R-22, very close mass flow requirement compared to R-22, and a minor three per cent drop-in efficiency. In addition. R-407C has been out of patent for several years. It is widely distributed and reasonably priced. As such, the industry has seen R-407C as the more common replacement for R-22 in comfort cooling applications.

READING THE FINE PRINT

Table 3 Comparative performance of R-22 replacements in AC applications

There is a considerable amount of misinformation regarding the pros and cons of various R-22 replacements. It is best to read the fine print to have the necessary information to make the best choice for a replacement.

For instance, in referring to Table 1 (Chemical composition of R-22 replacements), these replacements can be categorized in many ways, one important distinction is those refrigerants that have a hydrocarbon component (which allows the refrigerant to be used with mineral oil), and those that do not have a hydrocarbon component (which requires the use of POE).

One refrigerant manufacturer states this in its Conversion Guidelines: A lubricant change may not be required, but POE is always recommended for optimal performance. Confirming oil quality is important. Check the oil for moisture, acidity, and metal shavings or sediments. If the oil does not meet the desired specification, a complete oil change using POE is recommended. Systems with complex piping schemes or receivers could impede proper oil return so adding or changing over to POE is recommended. And oil change to POE is also recommended for systems designed to lubricate compressor bearings by pulling oil from the bottom of the oil sump, such as with Danfoss SM scroll and Trane 3-D compressors.

The fact is the refrigerant in question does not have a hydrocarbon component in its chemical composition. While there “might” be some systems with short and simple piping runs (package AC units) where one could get away with using mineral oil, this practice is not recommended by compressor manufacturers.

Another refrigerant manufacturer states: Because R-**** is a close match for R22 with similar cooling capacity, energy efficiency, pressures & low glide, it is suited for use in new equipment by Original Equipment Manufactures where it has significant advantages over R-****. Owing to the fact that R-**** is compatible with mineral & alkylbenzene lubricants, it is suitable for use as a Drop-in replacement for R22 in systems which contain an expansion device.

From this marketing blurb, one would think they had stumbled upon the Holy Grail of R-22 replacements but for the fine print: For the same duty R-**** has a higher volume flow rate than R22 which may require OEMs to increase appropriately the sizes of liquid lines to optimize performance, notably the following:

(1) Capillary tube: the length may need to be decreased, the diameter increased or a combination of both.
(2) Expansion valve: recommendation is to that the TX valve is sized to accommodate a mass flow 40% greater than R22. The bulb in a TXV typically used in a R502 system should be used.
(3) Liquid line: the diameter may need to be increased. On large systems with remote air-cooled condensers the liquid return line from the outlet of the condenser to the inlet of the receiver may also need to be modified.

However, OEMs should also note that the liquid viscosity of R-**** is significantly lower than that of R22 (see physical properties table) so that only modest changes to the liquid lines and expansion devices may be required.

To optimize system performance with R-****, evaporator and/or condenser capacities may need to be altered in some cases. The addition of a liquid/suction heat exchanger may also improve overall performance.

In systems where oil return could be an area of potential concern, e.g. containing a liquid receiver, flooded evaporators or long & complex pipelines, the replacement of up to 25% of the oil charge with a POE is recommended starting with an initial 10% followed by increments of 5% until the oil level stabilizes & returns to normal.

No additional commentary besides the red highlights is required, only to point out that with all of the “which may require” warnings, this particular refrigerant is anything other than a drop-in replacement for R-22. Do your own research and read the fine print.<>

Dave Demma holds a degree in refrigeration engineering and worked as a journeyman refrigeration technician before moving into the manufacturing sector where he regularly trains contractor and engineering groups. He can be reached at ddemma@uri.com.

Advertisem*nt

What to do about that pesky R-22 chiller: Part I - HPAC Magazine (2024)

FAQs

What is the replacement for R-22 chillers? ›

Freon MO99 is the gold standard for R-22 alternatives and was developed by the same scientists who engineered Freon R-22. The benefits of Freon MO99 include: Capacity — The ability of Freon MO99 to heat or cool a given space is closer to Freon R-22 than any other refrigerant on the market.

What are the major faults in chiller? ›

Problems with the refrigerant system, such as low refrigerant levels or a leak, could prevent the chiller from starting. Problems with the compressor, such as a failing motor or a seized compressor, may prevent the chiller from starting.

Why is my chiller not cooling enough? ›

1) Ensure a lower water temperature. 2) Increase the amount of water, possibly with automatic water valves to increase the amount of water. 3) Clear the condenser water pipe, possibly with the role of deoxygenation to remove. 4) Investigate the cause and replace or repair the cooling water pump (if installed).

What is the R-22 refrigerant conversion? ›

R-22 conversion is a process wherein an HVAC professional retrofits an old HVAC system to work using the R410A refrigerant rather than the phased-out R-22. You can't simply replace the refrigerant, because the two systems operate differently. For your current AC to take R-22, it must be modified.

Can you still buy R-22 Freon? ›

R-22 is no longer produced or imported into the United States, but it still exists inside some older HVAC units. If your unit uses R-22 and runs out, HVAC technicians may still have access to an existing recycled or recovered supply of this refrigerant and can service your unit as normal.

Do they still make R-22 condensers? ›

As of January 1, 2020, production and import of R22 refrigerant will be illegal in the United States. Of course, continued use of your air conditioner (AC) or heat pump system using R22 refrigerant is allowed.

What are the 4 main components of a chiller system? ›

Chillers consist of four essential components; an evaporator, a compressor, a condenser, and an expansion unit.

How many years does a chiller last? ›

The typical life cycle of a chiller depends on its type. On average, an air-cooled chiller's lifespan is anywhere from 15 years to 20 years. A water-cooled chiller is normally closer to 20 to 30 years. Where your chiller is located and the conditions it's under can also affect its life expectancy.

What causes chiller compressor failure? ›

Contaminants in the system: The presence of contaminants such as dirt, debris, moisture, or refrigerant impurities can damage compressor components, leading to failure. To prevent this, implement proper filtration systems, including suction line filters and liquid line dryers, to remove contaminants from the system.

What temperature should a chiller run at? ›

Generally, temperatures of between 45 and 50 degrees are suitable for cooling equipment. Pharmaceutical uses include use of chilled water in manufacturing and cool storage. Usually, 35 to 46 degrees is the recommended temperature for refrigeration during transport and storage of most cold-chain medications.

What is the most common problem with water-cooled equipment? ›

Fouling. This common problem is commonly caused by the three-Ds: dirt, dust, and debris, but can also be caused by other contaminants in the system such as migratory corrosion products or microbiological growth. Fouling can dramatically reduce system efficiency, driving up energy and operational costs.

What temperature should a chiller be set at? ›

A water chiller typically operates with a set point of 50°F or higher. However, if setpoints between 20°F - 48°F are required, special precautions must be taken to prevent freezing and possible damage.

Can I convert my R22 to R410A? ›

You cannot just switch refrigerants because R410-A and R-22 have different chemical properties. R410-A operates at a higher pressure. If you put R410-A into an R-22 system, the parts will rupture due to the increased force. You can convert your current system to one that runs on R-410A, but the cost will be high.

How much does it cost to convert R22 to R410A? ›

The cost to convert a central air conditioner from R-22 to R-410A can range anywhere from $2,000 to over $4,500 in the New Jersey area. The bottom line? If your AC unit is 8+ years old, it's usually not worth the cost to convert and you should just replace the entire R-22 unit with an R-410A unit.

Can I replace R22 with R134A? ›

The system will not operate efficiently with the R134A. It is designed for the more efficient R22. Using the R134A will make the compressor run more thus reducing the life of the compressor.

Can you replace 410A with R-22? ›

Also known as Freon, R22 was banned due to its contribution to ozone layer depletion and ecological harm. Freon is becoming scarcer and more expensive as a result. The new standard, R410A, is more environmentally friendly but cannot be substituted for R22 refrigerant.

Is 404a a good replacement for R-22? ›

1. The biggest problem of using refrigerant R404A to replace refrigerant R22 is the problem of lubricating oil. PVE ester oil must be used to replace the mineral lubricating oil for R22. Ester lubricants have high affinity with water and poor dehydration.

Which refrigerant blend is replacing R-22 in air conditioning? ›

If your compressor fails and you elect to change out the compressor as opposed to changing out the entire system, it may be wiser to change out the type of refrigerant to the replacement R22 refrigerants such as R407c. Doing so could save you a considerable amount should your system develop a leak in the years ahead.

What is a refrigerant blend replacing R-22 in a new residential and commercial air conditioning application? ›

R410a HFC (Difluoromethane, Pentafluoroethane) Is a near-azeotropic refrigerant blend replacing R-22 in residential and commercial airconditioning applications.

Top Articles
Latest Posts
Article information

Author: Tish Haag

Last Updated:

Views: 5879

Rating: 4.7 / 5 (47 voted)

Reviews: 86% of readers found this page helpful

Author information

Name: Tish Haag

Birthday: 1999-11-18

Address: 30256 Tara Expressway, Kutchburgh, VT 92892-0078

Phone: +4215847628708

Job: Internal Consulting Engineer

Hobby: Roller skating, Roller skating, Kayaking, Flying, Graffiti, Ghost hunting, scrapbook

Introduction: My name is Tish Haag, I am a excited, delightful, curious, beautiful, agreeable, enchanting, fancy person who loves writing and wants to share my knowledge and understanding with you.